| Batchers |

Low Cost,
Pulse Input Batch Controller
- 5
Digit Scaling Factor
- Display
Rate, Batch Size and
(Batch Total or Grand Total)
- Second
B Relay Programmable for Output at
Prewarn or selected Batch/Grand Total
- Pulse
Input - 10 kHz Max.
- Security
Lockout
- RS422/RS232
Serial Communication
- NEMA
4X / IP65 Front Panel
- 30mV
Magnetic Pickup Inputs
- 4-20mA
or 0-20mA Analog Output
|
The MINI-Batcher is a 6 digit totalizer and 4.5 digit
ratemeter with two relay outputs. One output is dedicated to
the batch amount (Preset A), the other can be activated for
Prewarn or Batch/Grand Total. The unit can count up to the
preset (reset to 0) or down from the preset (set to preset).
Start, Stop and Reset functions can be activated from the
front panel or remote inputs.
An analog output (assignable for Rate or Batch Amount) is
available for data logging.
Up to 99 units can communicate to a host computer on a single
RS232 or RS422 loop.
|

Economical Flow
Totalizer, Ratemeter and Batcher
- Multiple
Instrument Functions
- Menu
Selectable Hardware Features
- Two
Line LCD or VFD Display
- Automatic
Batch Overrun Compensation
- Isolated
Pulse Output Standard
- RS-232
Port Standard, RS-485 Optional
- DIN
Enclosure with Two Piece Connectors
- EZ
Setup Feature
- DDE
Server & HMI Software Available
|
The SUPERtrol-I LE Flow Computer satisfies the instrument
requirements for a variety of pulse producing flowmeter types
in liquid applications.
The alphanumeric display shows measured and calculated
parameters in easy to understand format. Single key direct
access to measurements and display scrolling is supported
The SUPERtrol-I LE can be programmed for rate/total indication
or batching. The various pulse inputs and outputs can be
“soft” assigned to meet a variety of common application
needs. The user “soft selects” the usage of each pulse
input while configuring the instrument.
The user can assign the standard RS-232 Serial Port for data
logging, transaction printing, or for connection to a modem
for remote meter reading. An optional RS-485 serial port using
Modbus RTU protocol is available.
A Service or Test mode is provided to assist the user during
startup system check out by monitoring inputs and exercising
outputs. The system setup can also be printed.
|
Multi-Function
Flow Totalizer,
Ratemeter and Batcher
- "EZ
Setup" Guided Setup for First Time Users
- Multiple
Instrument Functions
- Menu
Selectable Hardware & Software Features
- Two
Line LCD or VFD Display
- Universal
Viscosity Curve (UVC) and API Eq.
- Advanced
Batching Features: Overrun Compensation,
Autobatch Start, Print End of Batch
- Isolated
Outputs Standard
- RS-232
Port Standard, RS-485 Optional
- DIN
Enclosure with Two Piece Connectors
- Windows TM
Setup Software
- On
Board Data Logging
- DDE
Server & HMI Software Available
|
The SUPERtrol-I Flow Computer satisfies the instrument
requirements for a variety of flowmeter types in liquid
applications. Multiple flow equations and instrument functions
are available in a single unit with many advanced features.
The alphanumeric display shows measured and calculated
parameters in easy to understand format. Single key direct
access to measurements and display scrolling is supported
The versatility of the SUPERtrol-I permits a wide measure of
versatility within the instrument package. The various
hardware inputs and outputs can be “soft” assigned to meet
a variety of common application needs. The user “soft
selects” the usage of each input/output while configuring
the instrument.
The isolated analog output can be chosen to follow volume
flow, corrected volume flow, mass flow, temperature, or
density by means of a menu selection. Most hardware features
are assignable by this method.
The user can assign the standard RS-232 Serial Port for data
logging, transaction printing, or for connection to a modem
for remote meter reading.
A Service or Test mode is provided to assist the user during
start-up system check out by monitoring inputs and exercising
outputs and printing system setup.
|

Batch
Controller With Two Stage Valve Control
- Start/Stop
Buttons & Remote Inputs
- Separate
8 Digit K-Factors For Rate & Total
- Accepts
Pulse or Analog Inputs
- Displays
Rate, Total and Grand Total
- Security
Lockout with Missing Pulse Detection
- Scaled
Pulse Output
- Two
Way RS232/422 Communications Option
- 2
Setpoints For Two Stage Valve Control
- NEMA
4X (IP65) Front Panel
|
Featuring 8 digits of bright, .55 inch, alpha-numeric display,
the BATCHtrol II can accept up to 20,000 pulses per second of
digital count. The analog input versions accept inputs, such
as 4 to 20 mA or 1 to 5V. It uses a highly linear integrator
(V to F converter) to generate 0 to 10 kHz digital pulses. The
standard unit has two separate, 8 digit, floating decimal,
"K" factors to convert the inputs to meaningful
total and rate data. An optional 16 point K-factor can
linearize flow from nonlinear meter outputs. The user, with
the push of a button, can toggle back and forth to view the
total of the batch, the rate of flow or the grand total of
flow.
The BATCHtrol II may be thought of as two separate counters
and a ratemeter. The "batching" counter counts to
prewarn and preset numbers entered by the user and enables
separate control outputs. The "totalizing" counter
gives a cumulative reading or grand total. Finally, the
ratemeter counts the number of pulses per second and, with its
scaling feature, can provide gallons per minute or any other
rate measurement without the totalizer losing counts. At any
time, the user may view the total, the grand total or the rate
while never interrupting the counting process.
Setup is done through the front panel and the menu driven
software in the unit. Start-Stop control can be activated via
the front panel buttons or remote inputs.
The unit operates from either 110 VAC/12 to 27 VDC, or
optional 220 VAC/12 to 27 VDC. If AC power is used, two
built-in regulated 12 VDC @ 100 mA power supplies are offered.
They can be connected to provide +12 VDC and -12VDC or +24 VDC
to drive external devices. CMOS Logic is used to provide high
noise immunity and low power consumption with EEPROM to hold
data a minimum of 10 years if power is interrupted.
Up to 15 units can be connected to optional RS232 or RS422
communications port to set control points or access data.
|
|
|
|